Surge Protection Devices (SPDs): When AS/NZS 3000 Requires Them
By ARCK Electrical � Trade counter, North Parramatta � Reviewed May 2026
Quick Q&A - click to expand
Does every domestic install really need an SPD now? +
AS/NZS 3000:2018 with amendments recommends an SPD on every domestic board after a risk assessment - and most installers now treat it as a default specification rather than an optional upgrade. The cost is small ($80-$200 trade) and the protection scope (every appliance downstream) makes it a sensible standard. Some new estates and apartment specs now mandate it explicitly.
Type 1 vs Type 2 - which do I need? +
Type 2 is the default for almost every domestic and commercial install. Type 1 is needed only where direct lightning strikes are a real risk: rural acreage, tall isolated structures, properties near transmission infrastructure, or sites with external lightning rods that need to coordinate. If you're not sure, Type 2 covers ~95% of Australian residential installs.
How do I know when an SPD has reached end of life? +
Every SPD has a status indicator - usually a visible window on the front (green = OK, red = failed) or an LED. Surge events progressively degrade the internal varistors. When the indicator flips, replace the cartridge (or whole unit). Visual inspection during 6-monthly switchboard checks catches this; some units also have a dry contact for remote monitoring on commercial boards.
Does an SPD work with RCBOs and other protection? +
Yes - SPDs are independent of RCBOs / RCDs / MCBs and don't interfere with their operation. The SPD has its own dedicated backup MCB (per manufacturer's spec) on the supply side. RCBOs continue to protect their downstream final sub-circuits independently. Coordination is handled by the board manufacturer's compatibility chart for that brand's SPD + protection range.
What about Type 3 SPDs at the powerpoint? +
Type 3 sits at the point of use - built into a powerpoint, surge-protected power strip, or fixed equipment. It catches residual surges that pass the main-board Type 2. For a typical domestic install, Type 2 is enough. Type 3 adds value for valuable / sensitive equipment: medical electronics, server gear, high-end AV. Not usually a code requirement - a customer preference.

Surge protection devices (SPDs) used to be an optional upgrade. They're now effectively a default on new domestic switchboards under AS/NZS 3000 amendments. This guide covers what each type does, where it goes on the install, and the typical residential and commercial setup.
The three SPD types
AS/NZS 1768 (the lightning protection standard) and IEC 61643 classify SPDs into three types by where they sit in the installation:
| Type | Location | Protects against | Typical site |
|---|---|---|---|
| Type 1 | Main switchboard, on the supply side | Direct lightning strikes (10/350?s waveform) | Rural / elevated / lightning-prone properties; commercial sites with exposed mains |
| Type 2 | Main switchboard or sub-board | Transient overvoltages from the network and induced surges (8/20?s waveform) | The default on every modern domestic and commercial board |
| Type 3 | At the point of use (powerpoint, fixed equipment) | Residual surges that pass through upstream protection | Computer / AV / sensitive medical equipment |
For a typical Sydney domestic install, a Type 2 SPD on the main board is the standard pick. Type 1 is added where direct lightning strikes are a real risk (rural acreage, tall isolated buildings, sites near transmission infrastructure). Type 3 is a customer upgrade for protecting sensitive equipment downstream of the board.
What's changed in AS/NZS 3000
The 2018 edition with amendments significantly raised the profile of SPDs:
- Risk assessment recommended for every install - most installers now spec an SPD on every domestic board as standard practice
- SPD installation rules (clauses around protective bonding, disconnection time, downstream coordination) are spelled out
- Replacement and indication - every SPD must have a visible status indicator (window or LED) and be replaceable without disturbing the rest of the board
Most insurers also now favour insured properties where the switchboard has a Type 2 SPD - for the cost (typically $80-$200 trade for a domestic unit), it's a small upgrade that protects everything downstream.
In stock at ARCK
Surge protection and switchboard gear
Browse the full circuit protection range, or call the North Parramatta trade counter on (02) 9890 9693 if you want a hand picking the right one.
How an SPD sits on the board
A Type 2 SPD takes 1 or 2 modules on the DIN rail, usually right next to the main switch. It's wired between:
- Active(s) ? SPD (one per phase)
- Neutral ? SPD
- SPD ? main earth bar
When a transient overvoltage hits the active conductor, the SPD's internal varistors or gas discharge tubes conduct briefly to ground, clamping the voltage to a safe level. The energy flows to earth instead of into the downstream circuits.
The SPD needs a dedicated backup protection - typically an upstream MCB rated to the SPD manufacturer's spec (commonly 25A-63A depending on the unit). On Clipsal Resi MAX, Hager Resi9 and Connected Switchgear boards, this is a standard component matching the brand's SPD.
Surge protection devices on the shelf
Clipsal Resi MAX, Hager Resi9, NHP, Connected Switchgear - Type 1, Type 2 and 4-pole SPDs.
Browse circuit protection ?What it actually protects
A typical domestic SPD protects against:
- Switching surges from the distribution network - appliances cycling, neighbouring industrial loads, distribution faults
- Indirect lightning - strikes on the network or nearby that induce surges down the supply
- Inductive load switching - large motors, transformers, HVAC starting
What an SPD does NOT protect against:
- Direct lightning strikes to the building (that's Type 1)
- Sustained overvoltage (e.g., a broken neutral that lifts the phase voltage permanently) - that's an overvoltage protection device, different category
For domestic, the realistic protection scope is: an everyday network transient that would otherwise blow up consumer electronics, LED drivers, inverter circuits in appliances, and modern induction cooktops.
Sizing and selection
For a typical single-phase 80A or 100A domestic main:
- Imax (max discharge current): 20-40 kA Type 2 unit
- Up (residual voltage): ?1.5 kV for AC230V supply
- Modules: 1 or 2 module wide on the DIN rail
- Replaceable cartridges: preferred - when the SPD has absorbed enough surge events to be at end-of-life, swap the cartridge instead of the whole unit
Three-phase commercial: 4-pole Type 2 (3 phases + neutral) with matching Imax for the site fault current.
Compliance note
Electrical work in Australia must be carried out by a licensed electrician under AS/NZS 3000. SPD selection, board placement, backup protection sizing, and lightning risk assessment all fall within that scope. AS/NZS 1768 covers the broader lightning protection scheme where Type 1 or external lightning rods are involved.
Order from ARCK
We stock SPDs from Clipsal Resi MAX, Hager Resi9, NHP and Connected Switchgear - Type 2 domestic, Type 1 for rural / commercial, three-phase 4-pole, replaceable cartridges. Same-day pick-up from North Parramatta.
Browse the circuit protection range, or call the counter on (02) 9890 9693 to spec the right SPD for a specific board and supply authority. Mon-Fri 6:30am-5pm, Sat 7:30am-1pm.
In stock at ARCK
Surge protection and switchboard gear
Browse the full circuit protection range, or call the North Parramatta trade counter on (02) 9890 9693 if you want a hand picking the right one.